Cooper Bussmann 1000W Guía de instalación Pagina 41

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 42
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 40
42
FanOn/Offsetting
Parameter Fanon Fanoff
Load >500
W
<200
W
Extrusiontemp >60C <55C
RectifierDiode >70C <60C
DisplayPanelIndicators/Switches
‐ ‘Main’On/Offmomentaryswitch
‐ ‘Select’momentaryswitch
‐ 3x7‐segmentLEDdisplay
‐ ‘STATUS’LED(tricolor)
‐ BatteryVoltage’LED(Green)
‐ ‘BatteryCurrent’LED(Green)
‐ ‘OutputPower’LED(Green)
‐ Remotecommunicationcable,6‐wire,25ftlong(P/N31‐5267‐00)
UserMessages/Diagnostics
ThefollowingFaultcodesareprovidedondigitaldisplaywhensystemFault/Warningoccurs:
E01:DCInputUnder‐VoltageShutdown
E02:DCInputOver‐VoltageShutdown
E03:InverterOutputOverload(orShortCircuit)Shutdown
E04:InverterOver‐TemperatureShutdown
E05:DCInputUnder‐VoltageWarning
E06:InverterOutputOverloadWarning
E07:InverterOver‐TemperatureWarning
E08:Notused
E09:Notused
E10:ChargerOutputOverVoltageShutdown
E11:Batterynotacceptingcharge
E12:TransferRelayOver‐TemperatureShutdown