29
UtilitytoInverter
ACinputrecoveryfrom
InvertertoUtility
100VAC
UtilitytoInverterand
InvertertoUtility
hysteresis
5VACminimum
MaximumACoutputby‐
passcurrent
20Arms
ACtransfertime–
InvertertoUtility
20Secondsnominal
ACtransfertime–Utility
toInverter
<50ms
Timedelayontransfer
fromInvertertoUtility
20s+/‐2s
Voltages+/‐5V
Batter
Charger
ACinputoperatingrange
95–135VAC
ACinputrangewithfull
power
105V–135VAC
ACinputcurrentwithno
load
<0.50Arms
Inputcurrentfullload <6Arms(12‐110‐1000‐B2) 11.5Arms(12‐110‐1000‐B4,12‐110‐1800‐B4)
ACinputfrequency 60Hz+/‐1Hz
OperatingTemperature
Range
0Cto+50C(Allowfor1.5Adcchargecurrentreductionabove+40C)
DC Output Voltage:
Battery Type
Setting
O/P Voltage VDC (Tolerance +/- 0.2Vdc)
Bulk
Absorption Float
Fixed 13.5
13.5
13.5 13.5
Flooded
14.4
14.4 13.5
Gel
14.3
14.2 13.8
AGM
14.4
14.3 13.4
Comentarios a estos manuales