Cooper Bussmann BU-905U-L Wireless I/O Configuration Manual
Key Features
Feature Description For more information, see …
Mappings Lets you configure which inputs are sent to which outputs. Sending data to another station
Mappings can be triggered on a change of state (event reporting) using mappings on page 46.
or on a timed basis (periodic update). Outputs can be physical
outputs or Gateway registers.
Discrete signals Lets you monitor discrete (on or off) signals such as level
switches and alarms. The BU-905U-L-T has two discrete inputs.
The BU-905U-L-R has three discrete relay outputs
Analog signals Lets you monitor 4-20mA and 0-20mA current loop signals. Setting unit sensitivities
The BU-905U-L-T has one 0-20mA analog input. The BU-905U-L-R on page 52.
has one 0-20mA analog output
Millivolt signals Lets you measure millivolt signals (-10 – 100 mV) and thermocouple Working with thermocouple tables
(Thermocouple) signals with linearization for several different types of thermocouple on page 57 and Working with units
and cold junction compensation. on page 32.
The BU-905U-L-T has one millivolt input that you can use for
thermocouple input with or without cold junction compensation.
Pulsed signals Lets you count the number of times an input turns off and on, for Counting events by setting unit
example monitor pulses from a flow meter. pulsed inputs on page 53.
Setpoints Lets you control a remote digital output depending on the value of Setting setpoints on page 54.
an analogue input compared to user-configured setpoint values.
The BU-905U-L-T supports:
• Standard (fixed) setpoints; and
• Rotary setpoints – that determines threshold values using the
position of the rotary switch on the module.
System Status Lets you activate an alarm if the internal self-monitoring system BU-905U-L Installation Guide.
indicates a problem, or if the module loses power
Communication Status Lets you activate an alarm if the module hasn’t received any Handling communication failures
communication for a certain amount of time. by setting output reset times on
page 65.
Debounce Lets you set the amount of time an input needs to have differed
from its previous value before it is recognized as having changed.
This helps with noisy signals.
Sensitivities Lets you set the amount of change required of an input before the Setting unit sensitivities
BU-905U-L-T identifies the value as different from its previous value. on page 52.
Unit details Lets you create and update units and set unit-specific information. Working with units on page 32.
For more information, see the next sections.